Battery and Charger Cabinets & Enclosures

Exponential Power designs and builds custom DC enclosures for battery systems and/or chargers. A typical cabinet integrates batteries, racking and chargers into an indoor (NEMA 1 or 12) or outdoor (NEMA 3R) rated enclosure. There are many different options and accessories available, making every system unique and built to your site-specific needs. They can be constructed with batteries, battery/charger combinations, and even DC distribution panels. Batteries can be installed on pull-out drawers or fixed shelves.

Typical Industry Standards

      • NEMA Type 1, 3R, 12
      • UL Listed Type 1, 3R, 12
      • CSA Type 1, 3R, 12
      • IEC 60529

    NEMA Type 1 – Enclosures are for indoor use to provide a degree of protection to personnel against access to hazardous parts and to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt). This is a basic indoor cabinet that will include venting for batteries.


  • NEMA Type 3R – Enclosures are for indoor or outdoor use to provide a degree of protection to personnel against access to hazardous parts; to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt); to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (rain, sleet, snow); and that will be undamaged by the external formation of ice on the enclosure. This is a typical outdoor cabinet that will require rain hoods for the vents.

  • NEMA Type 12 – Enclosures are for indoor use to provide a degree of protection to personnel against access to hazardous parts; to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt and circulating dust, lint, fibers, and flyings); and to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (dripping and light splashing). This cabinet will require NEMA 12 vents and/or cooling fans.
  • Carbon steel (0.104 – 0.125″)
  • ANSI-61 gray powder coated finish
  • Continuously welded and ground smooth seams
  • Lifting eyes for easy handling
  • Concealed door hinges
  • Key / Padlocking handle
  • 3-point locking mechanism
  • Body stiffeners
  • Oil resistant gasket
  • Ground stud on door
  • Print pocket provided on door
  • Provision for mounting LED light
Part No. No. of Doors Length (in.) [w/ rain hoods] Width/Depth (in.) Height (in.) [w/ 6" legs & eye bolts] Vent/Fan Size (in.)
SBS-603624STD 1 36 [45] 24 60 [67.75] 6
SBS-723624STD 1 36 [44] 24 72 [79.75] 6
SBS-723636STD 1 36 [45] 36 72 [79.75] 6
SBS-903636STD 1 36 [45] 36 90 [97.75] 6
SBS-724824STD 1 48 [57] 24 72 [79.75] 6
SBS-724836STD 1 48 [57] 36 72 [79.75] 6
SBS-726024STD 1 60 [69] 24 72 [79.75] 6
SBS-726036STD* 1 60 [69] 36 72 [79.75] 6
SBS-907224STD* 2 72 [81] 24 90 [97.75] 6
SBS-907236STD* 2 72 [81] 36 90 [97.75] 6
SBS-8611230STD* 3 112 [121] 30 86 [93.75] 10
SBS-8614930STD* 4 149 [158] 30 86 [93.75] 10
  • Grill and washable filter kit
  • Fan kit (includes grill and filter)
  • Rain hood (for outdoor NEMA 3R applications)
  • Door-activated LED lighting
  • NEMA 12 vents and fan kit
  • Subpanel
  • Heater with built-in thermostat
  • Floor stand kit (6″ or 12″ stands available)
  • Drip shield
  • Viewing window
  • Batteries (Flooded LA, VRLA or Ni-Cad)
  • Battery rack and rack installation
  • Spill containment
  • Battery charger and charger installation
  • DC cabling